Always Committed to delivering Excellence
Khasra No. 291, Gali No. 2, Shalimar Village Industrial Area, Delhi-110088 INDIA
A Dual Source Energy Multifunction Meter is a specialized device used to monitor and measure energy consumption from two different power sources simultaneously. It provides accurate readings of electricity usage from both the main power grid and an alternative energy source, such as solar panels or wind turbines.
This advanced meter offers a comprehensive overview of energy consumption, allowing users to track and manage their usage from multiple sources effectively. By displaying real-time data, it enables users to make informed decisions about energy usage optimization, cost savings, and environmental impact reduction.
The EM6438-EM 6436 Dual Source Energy Meter is equipped with various features, including voltage, current, power factor, and frequency measurement capabilities. It also provides important information, such as kWh and kVAh readings, which are essential for billing and better understanding energy usage patterns.
Yokins Instruments Private Limited takes immense pride in being recognized as the leading Suppliers and traders of Dual source energy meter. With a steadfast commitment to quality and innovation, we have established a formidable reputation in the industry.
At Yokins Instruments, we understand the importance of a Dual Source Energy Meter at Best Price in India in today's dynamic power distribution systems. Our meters are specifically engineered to accurately measure energy consumption from different sources, allowing users to seamlessly monitor and optimize their energy usage.
Choose Yokins Instruments Private Limited as your Suppliers partner for all your Dual Source Projection Meter requirements, and experience excellence in energy monitoring and management.
RMS Voltage | 20 - 600Vrms (Accuracy :- +0.5% FS +1 dgt.) |
RMS Current | 0.020- 10.00Arms (Accuracy :- +0.5% FS +1dgt.) |
Active Power | 0.030- 6.000 KW (Accuracy :- +0.5% ES +1 dgt.) |
Power Factor | 03Llag-1.0-0.3 Lead (Accuracy :- + 0.01 PE +1 dgt.) |
Line Frequency | 45.00- 65.00 Hz (Accuracy :- £0.1Hz) |
Active Energy (KWh) | 000000.00 - 999999.99 Kwh (Accuracy Class 1,0.5) |
Apparent Energy (KVAh) | 000000.00 - 999999.99 KVAh (Accuracy Class 1,0.5) |
DG HOUR | HHHH.MM FORMAT (ACCURACY +-1 MIN) |
Faceplate /Lens | Polycarbonate Transparent |
Case/Housing Material | FR-ABS Black |
Connectors /Terminal | Nylon 66, 33%GF, Black/Brass |
Mounting Clamps | Sturdy, Moulded Glass filled nylon with screws. |
Decimal Point | Auto Scrolling |
Polarity Indication | L(Laggine/Inductive) or C(Leading/Capacitive) |
Under Range Indication | Error Code 01 Blinking when Current Non Detectable |
Dielectric Strength | 2.5KV @50 Hz 1 minute between Input -Auxiliary |
& Case - Terminals | |
Impulse Withstand | 3.5.KV, 1.2/50 micro Second |
Refresh Rate | Per8.0ms |
Maximum Overload | Voltage 1.2 Times Continuous, Current 2 Times Continuous |
Auxiliary Supply | 150-300V AC, 45-270V AC |
DC, 19-60V AC /DC | |
DG SENSING VOLTAGE | 24V-270V AC/DC |
VA Burden (Typical) | |
Auxiliary | <2.5 VA |
Voltage Input | <0.2 VA / Phase |
Current Input | <0.2 VA / Phase |
PT Primary Range | 50 to 500kV AC Programable |
PT Secondary Range | 50 to 500V AC Programable |
CT Primary Range | 1A to 50kA AC Programable |
CT Secondary Range | 0.5A to 5A AC Programable |
Metering Standard | IEC 62053-21/22 |
Installation Category | Cat II (IEC / EN61010 - 1) |
Pollution | Degree 2 (IEC / EN61010 - 1) |
Environment | |
Calibration | 27°C ± 5°C |
Operating | 0° to 50°C, RH <70% |
Storage | 10° to 60°C, RH < 70% |
Dielectric Strength | 2.5 KV at 50 Hz for 1 mm |
Insulation Resistance | > 20 MOhms at 500 V DC |