Always Committed to delivering Excellence
Khasra No. 291, Gali No. 2, Shalimar Village Industrial Area, Delhi-110088 INDIA
Yokins Instruments Private Limited is known as the leading Manufacturers and trader of Four Channel DC KWH Meters. These meters are specifically designed to accurately measure and monitor the consumption of electrical energy in a DC power system.
A Four Channel DC KWH Meter is a sophisticated device that offers the capability to monitor the energy usage of up to four different channels simultaneously. This feature proves to be highly beneficial in various applications where multiple energy sources or loads need to be monitored individually.
Being the Top 4 Channel DC Energy Meter Manufacturers in India, with a focus on precision and efficiency, Yokins Instruments Private Limited ensures that their 4 Channel DC Energy Meter - dc power meter provide accurate measurements and reliable performance. These meters are equipped with advanced features such as digital displays, data logging capabilities, and user-friendly interfaces, making them easy to operate and maintain.
As the best Manufacturers of 4 Channel DC Energy Meter in India, by choosing Yokins Instruments Private Limited, customers can rest assured that they are receiving high-quality DC Energy Meter 4 in 1, 6.5V-100V 100A that meet industry standards and deliver accurate energy consumption data for informed decision-making.
DC BUS Voltage | 0-200VDC (Accuracy - +0.5% FS +1 dgt.) |
DC Current | 075 mV or 50mV (VIA SHUNT) (Accuracy - +0.5%FS +1 dgt.) |
DC Power | 0.000-9999 KW or MW(Accuracy :- £ 0.5% ES +1 dgt.) |
DC Energy (KWh) | 000000 — 999999 kwh (Accuracy Class 18 0.5) |
Faceplate /Lens | Polycarbonate Transparent |
Case/Housing Material | FR-ABS Black |
Connectors /Terminal | Nylon 66, 33%GF,Black/Brass |
Mounting Clamps | Sturdy, Moulded Glass filled nylon with screws |
Decimal Point | Auto Scrolling |
Polarity Indication | Negative Polarity Indication Available On Demand |
Under Range Indication | Error Code 01 Blinking when Current Non Detectable |
Dielectric Strength | 2.5KV @50 Hz for 1 minute between Input -Auxiliary & Case - Terminals |
Impulse Withstand | 3.5.KV, 1.2/50 micro Second |
Refresh Rate | Per8.0ms |
Maximum Overload | Voltage: 1.2 Times Continuous, Current : 2 Times Continuous |
Auxiliary Supply | 36 To 72 VOLT DC (SELF-POWERED AUXILIARY AVAILABLE) |
Auxiliary | <2.5 VA |
Voltage Input | <0.2 VA |
Current Input | <0.2 VA / CHANNEL |
Metering Standard | IEC 62053-21/22 |
Installation Category | Cat II (IEC / EN61010 - 1) |
Pollution | Degree 2 (IEC / EN61010 - 1) |
EMISSION1 | CISPR22 CLASS A |
Fast Transient | 4KV IEC 61000-4-4 |
Surge withstand | IEC 6100-4-5 |
Damped Oscillatory | IEC 6100-4-12:ESD:IEC61000-4-2 |
SCALE | KV RANGE VIA PROGRAMMING POSSIBLE. |
SHUNT | 1A-50kA PROGRAMABLE. |
Environment | |
Calibration | 27°C ± 5°C |
Operating | 0° to 50°C, RH <70% |
Storage | -10° to 60°C, RH < 70% |
Dielectric Strength | 2.5 KV at 50 Hz for 1 mm |
Insulation Resistance | > 20 MOhms at 500 V DC |