Always Committed to delivering Excellence
Khasra No. 291, Gali No. 2, Shalimar Village Industrial Area, Delhi-110088 INDIA
Content for buy best Hand Driven Generator Metal Body Insulation Tester In Delhi.
Display | Analog display with 70mm scale length Knife Edge pointer with Anti-parallax mirror scale |
Tolerance of Voltage across measuring terminals |
Within + 10 % of the rated voltage |
Rotation Speed | 160 to 240 RPM |
Central Scale Mark | 1/50" of rated resistance value |
Insulation Resistance | 50 mega ohms at 500V DC |
Di-electric strength | 2KV @50Hz for 1 minute between case and terminals |
Ripple content at 160 RP | 10% of rated Voltage |
Housing material | Anti magnetic metal body |
Glass protection | With ABS flap |
Response Time | Less than 3 seconds |
Calibration | 27⁰C ± 5⁰C |
Operating | 0⁰ to + 60⁰C, RH<70% |
Storage | -10⁰ to +70⁰C, RH<70 |
Standard | IS 2992: 1987 |
Standard Accessories | 1. A pair of testing Leads 2. User manual and Test certificate 3. Rexin carrying case |